จำนวนสินค้า
Range | PowerLogic |
---|---|
Product name | PowerLogic PM3000 |
Device short name | PM3200 |
Product or component type | Power meter |
Power quality analysis | Up to the 15th harmonic |
---|---|
Device application | Multi-tariff Sub billing Power monitoring |
Type of measurement | Active and reactive power Apparent power Current Voltage Energy Power factor Frequency |
supply voltage | 100...277 V AC 45...65 Hz 173...480 V AC 45...65 Hz 100...300 V DC |
Network frequency | 50 Hz 60 Hz |
[In] rated current | 5 A 1 A |
type of network | 3P + N 3P 1P + N |
Power consumption in VA | 5 VA |
Display type | Backlit LCD |
Display resolution | 128 x 96 pixels |
Sampling rate | 32 samples/cycle |
Measurement current | 0.05…6 A 0.02…1.2 A |
Analogue input type | Current 0...5 A Current 0...1 A |
Measurement voltage | 50…330 V AC 45...65 Hz direct 50…330 V AC 45...65 Hz phase to neutral 80…570 V AC 45...65 Hz direct 80…570 V AC 45...65 Hz phase to phase 570…999000 V AC 45...65 Hz with external VT |
Frequency measurement range | 45…65 Hz |
Number of inputs | 0 |
Measurement accuracy | Current 0.3 % 0.5...6 A Current 0.5 % 0.1...1.2 A Voltage 0.3 % 50...330 V Voltage 0.3 % 80...570 V |
Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 Class 1 active energy conforming to IEC 62053-21 Class 2 reactive energy conforming to IEC 62053-23 Class C active energy conforming to EN 50470-3 |
Number of outputs | 0 |
Information displayed | Tariff (4) |
Communication port protocol | - |
Communication port support | - |
Data recording | Min/max of instantaneous values |
Mounting mode | Clip-on |
Mounting support | DIN rail |
Standards | BS EN 61557-12 IEC 61557-12 EN 61557-12 BS EN 61326-1 IEC 61326-1 EN 61326-1 BS EN 62052-11 IEC 62052-11 EN 62052-11 BS EN 62053-21 IEC 62053-21 EN 62053-21 BS EN 62053-22 IEC 62053-22 EN 62052-22 BS EN 62053-23 IEC 62053-23 EN 62052-23 BS EN 61010-1 EN 61010-1 IEC 61010-1 UL 61010-1 BS EN 61010-2-30 IEC 61010-2-30 EN 61010-2-30 UL 61010-2-30 ANSI C12.20 |
Product certifications | CE conforming to IEC 61010-1 (safety) CE conforming to EN 61557-12 (power monitor) CE conforming to EN/IEC 61326-1 (EMC) UKCA conforming to BS EN 61010-1 (safety) UKCA conforming to BS EN 61557-12 (power monitor) UKCA conforming to BS EN 61326-1 (EMC) CULus conforming to EN 61010-1 (safety) CULus conforming to UL 61010-1 (safety) EAC (sub-meter) RCM |
Width | 90 mm |
Depth | 70 mm |
Height | 95 mm |
Net weight | 0.26 kg |
Electromagnetic compatibility | Electrostatic discharge level 4 conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Surge immunity test level 4 conforming to IEC 61000-4-5 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 |
---|---|
Overvoltage category | III |
IP degree of protection | IP40 front panel: conforming to IEC 60529 IP20 body: conforming to IEC 60529 |
Relative humidity | 5…95 % at 50 °C |
Pollution degree | 2 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | < 3000 m |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 8.8 cm |
Package 1 Width | 13.2 cm |
Package 1 Length | 13.7 cm |
Package 1 Weight | 384 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 16 |
Package 2 Height | 30 cm |
Package 2 Width | 30 cm |
Package 2 Length | 40 cm |
Package 2 Weight | 6.567 kg |
Unit Type of Package 3 | P12 |
Number of Units in Package 3 | 128 |
Package 3 Height | 15 cm |
Package 3 Width | 80 cm |
Package 3 Length | 120 cm |
Package 3 Weight | 57.672 kg |